Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 59341 |
Response time | 10 ms (depending on bus cycle time) |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 when mounted on backplane |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm ) or screw terminals (0.08 ... 1.5 mm ) |
Mass | approx. 150 g |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** |
Power consumption | 0.15 W |
Electromagnetic compatibility | NE 21 |
Relative humidity | 95 % non-condensing |
Current | 286 mA |
Marking | II 3 G Ex nA IIC T4 Gc |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) |
EU-type examination certificate | PTB 03 ATEX 2042 X |
IECEx approval | BVS 09.0037X |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC |
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
Power | 1351 mW |
LED indication | Power LED (P) green: supply Status LED (I) red: line fault , red flashing: communication error |
Directive 2014/30/EU | EN 61326-1 |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Certificate | PF 08 CERT 1234 X |
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 |
Power dissipation | 3 W |
Voltage | 18.9 V |
Reaction time | 10 s |
Current limit | 70 mA |
Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) |
Open loop voltage | 16.6 V |
ATEX approval | PTB 03 ATEX 2042 X |
Open-circuit | > 15 kΩ |
Short-circuit | < 100 Ω |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Internal resistor | max. 90 Ω |
Interface | manufacturer-specific bus to standard com unit |
Coding | optional mechanical coding via front socket |
Internal capacitance | 1.65 nF |
Internal inductance | 0 mH |
Occupied slots | 2 |
Number of channels | 4 |
Field device | Solenoid Valve |
Field device [2] | audible alarm |
Field device [3] | visual alarm |
Environmental test | EN 60068-2-14 |
Lloyd Register | 15/20021 |
Bureau Veritas Marine | 22449/B0 BV |
DNV GL Marine | TAA0000034 |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
Input voltage range | 18.5 ... 32 V DC (SELV/PELV) booster voltage |