Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 61980 |
Материал | : 316 stainless steel : 316 stainless steel or Nickel Plated Brass : 316 stainless steel : Autotex F200XE EPDM |
Ambient temperature | -20 ... 40 °C (-4 ... 104 °F) at T6 -20 ... 60 °C (-4 ... 140 °F) at T4 |
Degree of protection | Type 4X, IP66 |
Connection | digital valve, terminals SV |
Mass | approx. 2.7 kg (6 lb) |
Rated voltage | 100 ... 240 V AC, 0.05 A, 50 ... 60 Hz 20 ... 30 V DC, 0.2 A |
Power consumption | 100 ... 240 V AC - 2.3 VA (without digital valve) 20 ... 30 V DC - 2.5 W (without digital valve) |
Relative humidity | 5 ... 95 %, non-condensing |
Operating mode | fully automatic (FA) |
Marking | II 3 G Ex ic ec nC [ic pzc] IIC T4 Gc (-20 °C ≤ Ta ≤ 60 °C) II 3 G Ex ic ec nC [ic pzc] IIC T6 Gc (-20 °C ≤ Ta ≤ 40 °C) II 3 D Ex ic tc [ic pzc, IIIC] IIIB T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (external version) II 3 D Ex ic tc [ic pzc, IIIC] IIIB T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (external version) II 3 D Ex ic tc [ic pzc] IIIC T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (internal version) II 3 D Ex ic tc [ic pzc] IIIC T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (internal version) |
Output type | (1) SPST, powered contacts from supply 0.08 A at 250 VAC 0.5 A at 30 VDC |
Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s , all axes |
Dimensions | 165 x 124 x 90 mm (6.5 x 4.9 x 3.5 in) |
Connection type | High pressure port: 1/8" NPTF Low pressure port: 1/8" NPTF |
IECEx approval | IECEx UL 14.0019X Ex ic ec nC [ic pzc] IIC T4 Gc (-20 °C ≤ Ta ≤ 60 °C) Ex ic ec nC [ic pzc] IIC T6 Gc (-20 °C ≤ Ta ≤ 40 °C) Ex ic tc [ic pzc, IIIC] IIIB T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (external version) Ex ic tc [ic pzc, IIIC] IIIB T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (external version) Ex ic tc [ic pzc] IIIC T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (internal version) Ex ic tc [ic pzc] IIIC T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (internal version) |
Supplementary information | Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Input type | mechanical contact |
Series | 5500 |
Number of volume exchanges | 4 ... 19 |
Hazardous environment | gas or dust |
LED indication | Membrane Pad K1: Green - Contact K1 is energized K2: Amber - Contact K2 is energized SV1/encl press.: Blue for safe pressure, Amber for valve on Bypass: Amber when bypass is active PT100 error: Red when fault in PT100 sensor |
Protective gas supply | instrument grade air or inert gas |
Safe pressure | - gas 0.7 mbar (0.3" H O) - dust 1.6 mbar (0.65" H O) |
Impact resistance | 30 g, 11 ms, all axes |
cULus | UL File E184741 Class I, Division 2, Groups A, B, C, D T4 (-20 °C ≤ Ta ≤ 60 °C) Class II, Division 2, Groups F, G, T4 (-20 °C ≤ Ta ≤ 60 °C) Class I, Division 2, Groups A, B, C, D T6 (-20 °C ≤ Ta ≤ 40 °C) Class II, Division 2, Groups F, G T6 (-20 °C ≤ Ta ≤ 40 °C) |
Contact loading | 3 A at 250 V AC , 30 V DC resistive load, 3 A at 30 V DC |
Fuse rating | AC: 2 A DC: 3.15 A : AC: 0.08 A DC: 0.5 A |
Input I | Temperature, up to 2 RTDs per unit |
Input II | 1 Bypass |
Inrush current | 3 A |
Directive 2014/30/EU | EN 61326-1:2013 |
Directive 2011/65/EU (RoHS) | EN 50581:2012 |
Shock resistance | EN 60068-2 |
Cable gland | M12 diameter 3 - 6.5mm M20 diameter 10 - 14mm : (3) M12x1.5 : 'P_C' (3) M20x1.5 |
Certificate | DEMKO 14 ATEX 1282X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-2:2014 , EN 60079-7:2015 , EN 60079-31:2014 |