Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 69850 |
Control elements | DIP-switch |
Ripple | ≤ 10 mV |
UL approval | E106378 |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 70 g |
Rated voltage | 16.8 ... 31.2 V DC |
Power consumption | 0.7 W |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Marking | II 3G Ex nA IIC T4 Gc |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 |
Core cross-section | 0.5 ... 2.5 mm (20 ... 14 AWG) |
Labeling | space for labeling at the front |
IECEx approval | IECEx UL 16.0116X |
Approved for | Ex nA IIC T4 Gc |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | DEMKO 16 ATEX 1750X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Accuracy | max. 0.1 % of full-scale value |
Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP |
Power dissipation | 0.6 W |
Configuration | via DIP switches |
Connection side | control side |
Input resistance | > 100 kΩ |
Signal type | Analog input |
Frequency range | 0 ... 10 Hz , 0 ... 100 Hz , 0 ... 5 kHz |
Influence of ambient temperature | < 100 ppm/K of full-scale value |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Input signal | 0/2 ... 10 V , max. 30 V |
Transmission range | linearity range: -1 ... 110 % |
Settling time | 70 ms , 7 ms , 150 µs |