Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 40400 |
Ripple | max. 50 µA |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Rated voltage | 18 ... 30 V DC |
Power consumption | ≤ 2.6 W at maximum load |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Labeling | space for labeling at the front |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Safety Integrity Level (SIL) | SIL 2 |
Display elements | LED |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Power dissipation | ≤ 1.4 W at maximum load |
Connection side | control side |
Load | 0 ... 600 Ω |
Input resistance | max. 265 Ω terminals 2-, 3; 5-, 6 , max. 330 Ω terminals 1+, 3; 4+, 6 |
Input/Output | basic insulation according to IEC 61010-1, rated insulation voltage 300 V |
Output/Output | functional insulation, rated insulation voltage 50 V AC |
Signal type | Analog input |
Frequency range | field side into the control side: band width with 1 V signal 0 ... 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 V signal 0.3 ... 7.5 kHz (-3 dB) |
Input/power supply | basic insulation according to IEC 61010-1, rated insulation voltage 300 V |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Influence of ambient temperature | ≤ 0.25 µA/K |
Protection against electrical shock | UL 61010-1:2012 |
Input signal | 0/4 ... 20 mA |
Available voltage | ≥ 16 V at 20 mA, terminals 1+, 3 |
Settling time | 200 µs |
Rise time/fall time | 100 µs |
External supply (loop) | 2 ... 30 V DC |