  • 1-channel signal conditioner
  • 230 V AC supply
  • Level sensing input
  • Adjustable range 5 kΩ ... 150 kΩ
  • Relay contact output
  • Minimum/maximum control
Параметр Значение
Общие характеристики
Артикул 13709
Control elements switch S1 Position I open circuit current: In the open circuit current principle, the relay becomes active when the limit is reached. Position II closed circuit current: In closed circuit current principle, the relay is activated when power is applied. The relay is deactivated when the limit is reached.
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals , max. 2.5 mm
Mass approx. 110 g
Rated voltage 207 ... 253 V AC, 45 ... 65 Hz
Power consumption approx. 0.8 W
Electromagnetic compatibility NE 21:2006
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Labeling space for labeling at the front
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Contact loading 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Display elements LEDs
Optional accessories - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03)
Energized/De-energized delay approx. 1 s / approx. 1 s
Configuration via DIP switches via potentiometer
Directive 2014/35/EU EN 61010-1:2010
Insulation coordination EN 50178:1997
Galvanic isolation EN 50178:1997
Control input min./max. control system: terminals 1, 2, 3 on/off control system: terminals 1, 3
Output 1 changeover contact
Connection side control side
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Signal type Digital Input
Open circuit voltage/short-circuit current approx. 10 V AC (approx. 1 Hz) / approx. 5 mA
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V
Response sensitivity 5 ... 150 kΩ , adjustable via potentiometer (20 turns)