Параметр | Значение |
Общие характеристики | |
Артикул | 69691 |
Switching frequency | < 3 Hz |
UL approval | E106378 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Rated voltage | 19 ... 30 V DC loop powered |
Power consumption | < 1.5 W |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Test input | see Functional Safety Manual |
Marking | II 3G Ex nC ec IIC T4 Gc [device in zone 2] |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Mechanical life | 5 x 10 switching cycles |
Labeling | space for labeling at the front |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
Contact loading | 253 V AC/3 A/cos φ 0.7; 30 V DC/3 A resistive load 253 V AC / 1/8 HP |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | PF 15 CERT 3932 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 |
Safety Integrity Level (SIL) | SIL 3 |
Display elements | LEDs |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Power dissipation | < 1.5 W |
Energized/De-energized delay | 150 ms / 150 ms |
Directive 2014/35/EU | EN 61010-1:2010 |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V |
Connection side | field side |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Signal type | Digital Output |
Minimum switch current | 10 mA / 24 V DC |
Test pulse length | max. 4 ms from DO card |
Pulse/Pause ratio | 150 ms / 150 ms |