Параметр | Значение |
Общие характеристики | |
Артикул | 54934 |
Материал | materials in contact with process : rod probe: 1.4404/316L rope probe: 1.4401/316 (optional PA coated) process connections: 1.4301/304, 1.4401/316, 1.4404/316L process membran, seal: Viton, EPDM |
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) |
Degree of protection | IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep) IP66, NEMA 4X |
Connection | gland M20 thread M20, G1/2, NPT1/2 device plug M12, 7/8 in |
Rated voltage | 11.5 ... 35 V DC, 2-wire 10.4 ... 48 V DC, 4-wire 90 ... 253 V AC, 50/60 Hz |
Construction type | device with rod probe device with rope probe |
Measurement range | rod probe: 4 m (13 ft) rope probe: 45 m (148 ft) |
Output signal | 4 ... 20 mA 2 x 4 ... 20 mA |
Process connection | threads: G1-1/2, NPT1-1/2 flanges: DIN EN from DN40, ANSI from 1-1/2", JIS from DN40 |
Measuring method | The device is a measuring system that functions according to the time-of-flight method. The distance from the reference point (process connection of the measuring device) to the product surface is measured. |
IECEx approval | see instruction manuals (SI) |
Designation | see technical information (TI) |
EC-Type Examination Certificate | see instruction manuals (SI) |
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-1:2007 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 60079-31:2009 |
Communication | 4 ... 20 mA HART (standard) PROFIBUS PA (option) |
Accuracy | digital: - measuring range up to 15 m (49 feet): ±2 mm (0.08 inch) - measuring range > 15 m (49 feet): ±10 mm (0.39 inch) analog: 0.02 % sum of non-linearity, non-repeatability and hysteresis included in the maximum measured error |
Directive 2014/35/EU | EN 61010-1:2010 |
Measured variable | distance between reference point and product surface |
Process pressure (static pressure) | -1 ... 16 bar (-14.5 ... 232.1 psi) |
Overspill protection | see approval (ZE) |
Process temperature | -30 ... 150 °C (-22 ... 302 °F) |
Dielectric constant | rod probe: DC ≥ 1.6 rope probe: DC ≥ 1.6 |
Telecommunications | radio license FCC |