Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 64557 |
Control elements | Control panel |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | 300 g |
Rated voltage | 19 ... 30 V DC |
Power consumption | 3.3 W |
Electromagnetic compatibility | NE 21:2006 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Current | 11.9 mA |
Resolution | max. 2 µA |
Marking | II 3G Ex nA nC IIC T4 Gc |
Output signal | analog |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Mechanical life | 10 switching cycles |
Labeling | space for labeling at the front |
EU-type examination certificate | BASEEFA 07 ATEX 0174 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Power | 4 mW |
Rated current | approx. 140 mA at 24 V DC |
Contact loading | 253 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (BASEEFA 07 ATEX 0174) 50 V AC/1 A/cos φ > 0.7; 30 V DC/1 A resistive load (Pepperl+Fuchs self-declaration) |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | PF 07 CERT 1141 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Display elements | LEDs , display |
Accuracy | < 20 µA, 10 µA typ. |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Power dissipation | 2.7 W |
Fault signal | downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Configuration | via operating buttons via PACTware |
Control drawing | 116-0129 |
Directive 2014/35/EU | EN 61010-1:2010 |
IECEx certificate | IECEx BAS 07.0047 |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC |
Voltage | 1.1 V |
Maximum safe voltage | 253 V (Attention! U is no rated voltage.) |
Other outputs | HART communicator on terminals 22, 24 |
Connection side | control side |
Load | max. 650 Ω , source mode |
Input resistance | 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6) |
Signal type | Analog input |
Relay | programmable either for fault or trip value (with direction, hysteresis and delay) |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA |
Programming interface | programming socket |
Influence of ambient temperature | < ± 2 µA/K |
Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Voltage range | 5 ... 30 V , sink mode from external supply |
Current range | 4 ... 20 mA , (source or sink mode) |
Collective error message | Power Rail and LED red |
Available voltage | ≥ 15.5 V at 20 mA, short-circuit protected |
Equipment | terminals 2, 5/3 |
Conformity | HART field device input (revision 5 to 7) |
Duration of measurement/Response delay | HART message acquisition time plus 100 ms |
Output I, II/III, IV | functional insulation acc. to IEC 62103, rated insulation voltage 250 V |
Output I, II, III, IV/other circuits | reinforced insulation acc. to IEC 62103, rated insulation voltage 300 V |
Output V/VI/VII/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 V |
Output I, II, III, IV | terminals 10, 11; 11, 12; 16, 17; 17, 18 , non-intrinsically safe |
Output V, VI, VII | terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 , non-intrinsically safe |