Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 73760 |
Switching frequency | min. 0.1 Hz max. 5 kHz |
Ambient temperature | -50 ... 75 °C (-58 ... 167 °F) hazardous area -50 ... 85 °C (-58 ... 185 °F) safe area |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP20 |
Mass | approx. 290 g |
Rated voltage | 9 ... 32 V |
Electromagnetic compatibility | NE 21:2011 |
Relative humidity | ≤ 95 % non-condensing |
Mounting | mounting on DIN rail in cabinet |
Time delay before availability | 2 ms |
Current | 43 mA |
Pollution degree | 2 |
Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC |
Output type | Low power valve , channels 1, 4, 7, 10 |
Vibration resistance | 5 g , 10 ... 150 Hz |
Connection type | plug-in terminals , spring terminal and screw terminal |
Housing material | Polycarbonate |
EU-type examination certificate | BVS 16 ATEX E 075 X |
IECEx approval | IECEx BVS 16.0051X |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Input type | Sensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
Power | 96 mW |
Rated current | max. 23 mA |
FM approval | pending |
Directive 2014/30/EU | EN 61326-1:2013 |
Shock resistance | 15 g , 11 ms |
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-7:2015 |
Bus | up to 2.5 mm |
Accuracy | 0.5 % of the measured value |
Directive 2014/35/EU | EN 61010-1:2010 |
Galvanic isolation | EN 60079-11 |
Design / Mounting | Cabinet installation |
Fieldbus type | PROFIBUS PA |
DIP switch | Address setting , write protection , simulation |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Marine approval | pending |
Fieldbus standard | IEC 61158-2 |
LED PWR | green: on, bus voltage existent |
Voltage | 9 V |
Maximum safe voltage | 253 V |
Line fault detection | lead breakage , short circuit |
Pulse duration | min. 80 µs |
Polarity | not polarity sensitive |
Inputs | up to 2.5 mm |
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |
FDE (Fault Disconnect Equipment) | 6.7 mA |
LED COM ERR | red, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error |
LED CHANNEL ERROR | red, flashing: lead breakage/short circuit; off: no error |
Number of outputs | 4 |
Number of inputs | 12 |
Supply voltage | 6.6 V |
Supply current | 1.5 mA |