Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 71777 |
Ripple | ≤ 10 % |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP20 |
Connection | terminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE |
Mass | 180 g |
Rated voltage | 24 ... 26 V |
Electromagnetic compatibility | NAMUR NE 21 |
Relative humidity | < 95 % non-condensing |
Mounting | DIN rail mounting |
Pollution degree | max. 2, according to IEC 60664 |
Vibration resistance | 1 g 10 ... 150 Hz |
CSA approval | CSA 16.70064204 |
Connection type | Terminals |
Housing material | Polycarbonate |
Core cross-section | up to 2.5 mm |
IECEx approval | IECEx TUR 16.0006X |
Group, category, type of protection, temperature class | II 3G Ex ec IIC T4 Gc |
Approved for | Ex ec IIC T4 Gc |
Rated current | max. 400 mA |
Directive 2014/30/EU | EN 61326-1:2013 |
Shock resistance | 15 g 11 ms |
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 |
Power dissipation | max 2.5 W |
Design / Mounting | Cabinet installation |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Fieldbus standard | EN 50170/2 |
LED PWR | green: Power on |
Statement of conformity | TÜV 16 ATEX 7831 X |
Terminating impedance | 100 Ω , integrated |
Climatic conditions | DIN IEC 721 |
Switch | PROFIBUS DP terminator |
Baud rate | 1.5 MBit/s max. |
PROFIBUS DP/Supply | basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC |
LED DP/ERR | red 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected |
PROFIBUS DP | PROFIBUS with RS-485 transmission technology |
PROFIBUS DP/PROFIBUS PA | functional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC |
PROFIBUS PA/Supply | basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 V DC |
LED PA | red 2 Hz flashing: No PA communication or overload Off: PA communication OK |