Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 6785 |
Ripple | ≤ 10 % |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -20 ... 85 °C (-4 ... 185 °F) |
Degree of protection | IP20 |
Connection | Power Rail or terminals 40, 55+, 41, 56- |
Housing | 100 mm x 115 mm x 107 mm |
Mass | approx. 600 g |
Rated voltage | 9 ... 32 V DC (supplied switch S2 in pos. I) 0 V DC (not supplied switch S2 in pos. II) |
Electromagnetic compatibility | NAMUR NE 21 |
Relative humidity | < 75 % |
Mounting | DIN rail mounting |
Current | 141 mA |
Pollution degree | max. 2, according to IEC 60664 |
Marking | II 3G Ex ec IIC T4 Gc |
Connection type | Terminals |
Core cross-section | up to 2.5 mm |
EU-type examination certificate | PTB 00 ATEX 2036 |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Approved for | Class I, Division 2, Groups A, B, C, D / Class I, Zone 2, Group IIC T4 |
Power | 1.2 W |
Rated current | max. 70 mA |
FM approval | CoC 3008872 |
Directive 2014/30/EU | EN 61326-1:2013 |
Certificate | PF 15 CERT 3527 X |
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 |
Control drawing | No. 116-0190 |
Galvanic isolation | EN 50178, EN 50020 |
Fieldbus standard | IEC 61158-2, ISA S 50.02 part 2 |
Voltage | 15 V |
Terminating impedance | 100 Ω switchable off and on via rotary switch S1: 1 -> on; 0 -> off |
Field-side/Host-side | safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
Host-side/Supply | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 V |
Field-side/Supply | safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
All circuits/FE | functional insulation acc. to DIN EN 50178, rated insulation voltage 253 V |
Climatic conditions | DIN IEC 721 |
Classification | 3K3 |