Параметр | Значение |
Общие характеристики | |
Артикул | 59297 |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP20 |
Mass | 360 g |
Rated voltage | 9 ... 32 V |
Electromagnetic compatibility | NE 21:2011 |
Relative humidity | ≤ 95 % non-condensing |
Mounting | mounting on DIN rail in cabinet |
Marking | II 3 G Ex nA IIC T4 Gc |
Vibration resistance | 5 g , 10 ... 150 Hz |
CSA approval | CoC 3025732C |
Connection type | plug-in terminals , spring terminal and screw terminal |
Housing material | Polycarbonate |
Grounding | grounding of thermoelements possible |
EU-type examination certificate | PTB 03 ATEX 2237 |
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Number | 8 |
Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc |
Rated current | max. 23 mA |
FM approval | CoC 3025732 |
Directive 2014/30/EU | EN 61326-1:2013 |
Shock resistance | 15 g , 11 ms |
Certificate | PTB 03 ATEX 2238 X |
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 |
Bus | see Statement of Conformity |
Galvanic isolation | EN 60079-11 |
Design / Mounting | Cabinet installation |
Fieldbus type | PROFIBUS PA |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Marine approval | DNV A-14038 |
Fieldbus standard | IEC 61158-2 |
LED PWR | green: on, bus voltage existent |
Voltage | 24 V |
Internal measurement cycle | for all sensor types max. 1 s |
Input | see EC-Type Examination Certificate |
Profile | 3.02 |
Influence of ambient temperature | see table 3 |
Cold junction compensation | ± 0.5 °C (32.9 °F) |
Firmware update | via separate plug connection |
Polarity | not polarity sensitive |
Inputs | see EC-Type Examination Certificate |
FDE (Fault Disconnect Equipment) | 6.7 mA |
LED COM ERR | red, continuous lightning: hardware error; red, flashing: no bus activities or bus fault; off: no error |
LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange; off: no error |
Sensor types | see table 1 |
Error detection | lead breakage, wiring error, hardware device error |
Common mode voltage | Input to Input 600 V |
Resolution/accuracy | see table 2 |
Linearization | T/C input 0.1°C RTD input 0.03°C |
Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |