Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 54334 |
UL approval | E106378 |
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) |
Degree of protection | IP20 |
Mass | see table "Technical data depending on model" |
Rated voltage | max. 31 V |
Electromagnetic compatibility | NE 21:2011 |
Relative humidity | < 95 % non-condensing |
Mounting | DIN rail mounting |
Current | 46 mA switch 1, position 1 65 mA switch 1, position 2 |
Marking | II 3 G Ex nA [ic] IIC T4 Gc II (3 D) [Ex ic Dc] IIIC |
Vibration resistance | 1 g , 10 ... 150 Hz |
Dimensions | see table "Technical data depending on model" |
Connection type | pluggable , screw terminal or spring terminal |
Housing material | Polycarbonate |
Core cross-section | see table 2 |
EU-type examination certificate | TÜV 12 ATEX 098651 X |
IECEx approval | IECEx TUN 12.0015X |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Approved for | Ex nA [ic] IIC T4 Gc [Ex ic Dc] IIIC |
Rated current | max. 32 mA switch 1, position 1 max. 43 mA switch 1, position 2 |
Directive 2014/30/EU | EN 61326-1:2013 |
Shock resistance | 15 g 11 ms |
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 |
Control drawing | 116-0406 |
Design / Mounting | Cabinet installation |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Marine approval | DNV A-14038 |
Terminating resistor | external type M-FT 100 Ω +/- 10 % |
Fieldbus standard | IEC 61158-2 |
Short-circuit current | 46 mA switch 1, position 1 57 mA switch 1, position 2 |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
Voltage | 32 V |
Climatic conditions | IEC 60721 |
Maximum safe voltage | 35 V |
Surge protection | Trunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V |
Switch | configuration of short-circuit current/rated current |
Inductance | 0.125 mH switch 1, position 1 0.25 mH switch 1, position 2 |
Capacitance | 60 nF |
Number of outputs | see table "Technical data depending on model" |
Number of devices per output | 1 |
Self current consumption | see table "Technical data depending on model" |
Voltage drop main cable/outputs | max. 1.2 V |
Voltage drop trunk In/Out | 0 V |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
LED SPURS | red: 2 Hz flashing in short-circuit condition |