Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Intrinsically safe Ethernet Isolator EI-0D2-10Y-10B

Intrinsically safe Ethernet Isolator EI-0D2-10Y-10B
Intrinsically safe Ethernet Isolator EI-0D2-10Y-10B

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 32275
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Galvanic Isolation I.S. to non-I.S. Port
  • 10/100 MBit/s according to IEEE 802.3/.3u
  • Installation in Zone 2, Ethernet in Zone 1 or Zone 0
  • Standard Ethernet patch or crossover cable
  • DIN-Rail mounted and OEM Version
Параметр Значение
Общие характеристики
Артикул 32275
Ambient temperature -40 ... 60 °C (-40 ... 140 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Degree of protection IP20 according to EN 60529
Mass 195 g
Rated voltage 19.2 ... 35 V DC
Relative humidity ≤ 95 % non-condensing
Mounting DIN rail mounting
Operating mode Half/Full Duplex
Transfer rate 10/100 Mbit/s , Auto-Negotiation
Pollution degree max. 2, according to IEC 60664
Marking II (1) G [Ex ia Ga] IIB , II (1) D [Ex ia Da] IIIC , II 3(1)G Ex nA [ia Ga] IIB T4 Gc II 3 (1D) G Ex nA [ia IIIC Da] IIB T4 Gc I (M1) [Ex ia Ma] I
Vibration resistance 1 g 10 ... 150 Hz
CSA approval CSA 15.70016295
Connection type Terminals
Housing material Polyamide PA 66
Core cross-section up to 2.5 mm
EU-type examination certificate PTB 07 ATEX 2025 X
IECEx approval IECEx PTB 09.0053X
Approved for [Ex ia Ga] IIB [Ex ia Da] IIIC Ex nA [ia Ga] IIB T4 Gc Ex nA [ia IIIC Da] IIB T4 Gc [Ex ia Ma] I
Rated current 150 ... 100 mA
Directive 2014/30/EU EN 61326-1:2013
Shock resistance 15 g 11 ms
Directive 2014/34/EU EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
Power dissipation 3 W
Control drawing 116-B032
Galvanic isolation EN 50020
Patents This product may be covered by the following patent: US7,687,791
LED PWR green: Power on
Climatic conditions DIN IEC 721
Maximum safe voltage 253 V AC
Ethernet IEEE 802.3 , IEEE 802.3u
Cable type CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/Ω of all strand combinations
Connector pinout socket ; TIA/EIA-568-B
Intrinsically safe port 10 BASE-T/100 BASE-TX
Non-intrinsically safe port 10 BASE-T/100 BASE-TX
I.S. cable length typ. 100 m/20 °C
Total cable length typ. 200 m/20 °C
Number of isolators max. 2 in series connection
LED ACT yellow: communication active
LED 10/100 yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено