Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 89990 |
Control elements | 2 push buttons: - restore HART configuration - restore communication configuration DIP switches: - baud rate - RS-485 address - RS-485 termination - security mode |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP66/IP67 |
Connection | UTP, STP or FTP |
Mass | approx. 1 kg |
Rated voltage | 20 ... 30 V DC SELV/PELV |
Power consumption | < 5 W |
Relative humidity | 5 ... 95 %, noncondensing |
Mounting | panel mounting |
Transfer rate | max. 115 kBit/s |
Marking | II 3 G Ex nA IIC T4 Gc |
Protocol | HART |
Vibration resistance | EN 60068-2-6 |
Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands |
EU-type examination certificate | FM 12 ATEX 0061 |
IECEx approval | IECEx FMG 12.0002 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Cable length | max. 1200 m , depending on cables and transfer rate |
Approved for | Ex nA IIC T4 Gc , Ex nAc T4 |
FM approval | Coc3042646 |
Directive 2014/30/EU | EN 61326-1:2013 |
Shock resistance | EN 60068-2-27 |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Communication | WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - transmission rate: 250 kBit/s - maximum transmit power: +10 dBm (EIRP) - transmission range: outdoor 250 m, indoor 50 m (under reference conditions) - communication standard: WirelessHART acc. to IEC 62591 |
Display elements | LED PWR (power supply status), one green LED LED COM (communication status), three yellow LEDs LED FLT (fault signal), one red LED |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 |
Interface | omnidirectional dipole antenna, removable |
Interface/power supply | basic insulation according to IEC 61140, rated insulation voltage 50 V |
Bus termination | integrated termination resistor , adjustable via DIP switch and software |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 , FCC ID: SJC-M2140 |
Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation |
Interface 2 | RS-485 |
Daisy-chain capability | supported by duplicated connection terminals |
Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 V |