Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Universal Temperature Converter KFD2-UT2-Ex2-1

Universal Temperature Converter KFD2-UT2-Ex2-1
Universal Temperature Converter KFD2-UT2-Ex2-1

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 55904
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Usable as signal splitter (1 input and 2 outputs)
  • Voltage output 0/1 V ... 5 V
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511
Параметр Значение
Общие характеристики
Артикул 55904
Ripple within the supply tolerance
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass approx. 130 g
Rated voltage 20 ... 30 V DC
Electromagnetic compatibility NE 21:2006
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Current 22 mA
Marking II 3G Ex nA II T4
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Labeling space for labeling at the front
EU-type examination certificate CESI 04 ATEX 143
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Power 50 mW
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate TÜV 02 ATEX 1797 X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
Safety Integrity Level (SIL) SIL 2
Display elements LEDs
Optional accessories - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) - FDT framework PACTware 4.1 - device type manager DTM Interface Technology - adapter K-ADP-USB-AB
Fault signal downscale 0 V or 0.5 V, upscale 5.375 V
Configuration via PACTware
Control drawing 116-0314 (cCSAus) 116-0347
IECEx certificate IECEx TUN 07.0003 IECEx CML 16.0126X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex nA IIC T4 Gc
Voltage 9 V
Maximum safe voltage 250 V (Attention! The rated voltage is lower.), RS 232
Connection side control side
Reaction time worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Input Ex ia
Input resistance ≥ 1 MΩ (-100 ... 100 mV)
Measuring current approx. 200 µA with RTD
Signal type Analog input
Programming interface programming socket
Influence of ambient temperature deviation of CJC included: ± (0.0015 % of measurement value in K + 0.0075 % of span)/K ΔT ± (0.02 K + 0.005 % of measurement value in °C + 0.0075 % of span)/K ΔT ± (0.01 % of measurement value + 0.0075 % of span)/K ΔT ± 0.0075 % of span/K ΔT ΔT = ambient temperature change referenced to 23 °C (296 K)
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Protection against electrical shock UL 61010-1:2004
Power dissipation/power consumption ≤ 0.8 W / 0.8 W
Lead resistance max. 50 Ω per line
After calibration ± (0.06 % of measurement value in K + 0.1 K (4-wire connection)) ± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) this includes ± 0.8 K error of the cold junction compensation ± 50 µV ± 0.05 % of full scale, (excludes errors due to lead resistance) 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span; 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span
RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760)
Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensation external and internal
Inputs terminals 1, 2, 3, 4, 5, 6 (for passive equipment)
Types of measuring 2-, 3-wire connection
Measurement loop monitoring sensor breakage
Voltage output 0 ... 5 V or 1 ... 5 V ; output resistance: ≤ 5 Ω ; load: ≥ 10 kΩ
Influence of supply voltage < 0.01 % of span
Output/supply, programming input functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided.

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено