Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 88927 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Rated voltage | loop powered |
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Current | 93 mA |
Marking | II 3G Ex nA II T4 [device in zone 2] |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
Labeling | space for labeling at the front |
EU-type examination certificate | BAS 98 ATEX 7343 X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Rise time | ≤ 5 ms at bounce from 4 ... 20 mA and U < 24 V |
Power | 585 mW |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | TÜV 99 ATEX 1499 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Safety Integrity Level (SIL) | SIL 2 |
Accuracy | 1 % |
Power dissipation | at 40 mA and U < 22 V: 700 mW per channel at 40 mA and U > 22 V: 1.2 W per channel |
Control drawing | 116-0438 (cULus) |
IECEx certificate | IECEx BAS 05.0004X IECEx CML 19.0040X |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
Short-circuit current | at U > 24 V: ≤ 65 mA |
Voltage | 25.2 V |
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Signal type | Analog input/analog output |
Influence of ambient temperature | ≤ ± 2 µA/K at U ≤ 20 V; ≤ ± 5 µA/K at U > 20 V |
Protection against electrical shock | UL 61010-1:2012 |
After calibration | ≤ ± 200 µA; incl. calibration, linearity, hysteresis and load fluctuations at the field side up to a load of 1 kΩ and current ≤ 20 mA at 20 °C (68 °F) |
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Transfer current | ≤ 40 mA |