  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Voltage input -10 V ... 10 V
  • Voltage output -10 V ... 10 V
Параметр Значение
Общие характеристики
Артикул 864
Ripple within the supply tolerance
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Rated voltage 20 ... 35 V DC
Electromagnetic compatibility NE 21
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Current 4.2 mA
Marking II 3G Ex ec IIC T4 Gc [device in zone 2]
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Labeling space for labeling at the front
EU-type examination certificate BAS 01 ATEX 7262
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rise time ≤ 0.4 ms
Power 19 mW
Rated current < 25 mA
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate BASEEFA 10 ATEX 0079X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018
Display elements LED
Optional accessories - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)
Control drawing 116-0132
IECEx certificate IECEx BAS 10.0040X
IECEx marking Ex ec IIC T4 Gc
Voltage 18 V
Maximum safe voltage 250 V (Attention! The rated voltage is lower.)
Connection side control side
Input resistance min. 10 MΩ
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Signal type Analog input
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supply functional insulation, rated insulation voltage 50 V AC
Influence of ambient temperature < 0.005 % of range per K
After calibration ± 5 mV at 20 °C (68 °F)
Output resistance max. 20 Ω
Transmission range -10 ... 10 V
Cut-off frequency 1.2 kHz (-3 dB)
Offset voltage/current < 2 mV / < 7 nA