Параметр | Значение |
Общие характеристики | |
Артикул | 53116 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 120 g |
Rated voltage | loop powered |
Electromagnetic compatibility | NE 21:2007 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Voltage drop | see note |
Current | 4 ... 20 mA (linear transmission 1 ... 22 mA) |
Marking | II 3G Ex nA IIC T4 Gc |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 |
Labeling | space for labeling at the front |
EU-type examination certificate | PTB 02 ATEX 2064 |
Rise time | ≤ 20 µs at 0 Ω, ≤ 600 µs with 800 Ω load |
FM approval | device with FM approval on request |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | PF 11 CERT 0902 X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Safety Integrity Level (SIL) | SIL 2 |
Power dissipation | 150 mW at 20 mA and U < 24 V |
Voltage | ≥ 16 V for supply voltage > 21 V |
Load | ≤ 800 Ω (at 20 mA) |
Signal type | Analog input/analog output |
Influence of ambient temperature | < 0.5 µA/K |
Damping | approx. 3 dB |