Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 58048 |
Control elements | DIP-switch |
Ripple | ≤ 10 % |
Switching frequency | ≤ 5 kHz |
Response time | ≤ 200 µs |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Rated voltage | 19 ... 30 V DC with external resistance > 2 kΩ, e. g. 16-channel ProSafe DI card SDV144 from Yokogawa |
Electromagnetic compatibility | NE 21:2011 , EN 61326-3-2:2008 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Current | 17.1 mA |
Marking | II 3G Ex ec IIC T4 Gc |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Labeling | space for labeling at the front |
EU-type examination certificate | BASEEFA 13 ATEX 0080 |
IECEx approval | IECEx BAS 13.0046 IECEx CML 19.0147X |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
Power | 45 mW (linear characteristic) |
Rated current | 35 ... 25 mA |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | CML 19 ATEX 4410 X |
Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
Safety Integrity Level (SIL) | SIL 2 |
Display elements | LEDs |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Power dissipation | ≤ 750 mW |
Configuration | via DIP switches |
Control drawing | 116-0374 (cULus) |
Voltage | 10.5 V |
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Connection side | control side |
Input | Ex ia |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/Output | basic insulation according to EN 50178, rated insulation voltage 50 V |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Signal type | Digital Input |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/power supply | basic insulation according to EN 50178, rated insulation voltage 50 V |
Protection against electrical shock | IEC 61010-1:2010 |
Output I, II | signal or error message, passive transistor output (resistive) 0-signal: 33 kΩ ± 5 % + voltage drop 6.5 V ± 0.5 V 1-signal: voltage drop 6.5 V ± 0.5 V fault: > 100 kΩ |
Collective error message | Power Rail |
Pulse/Pause ratio | min. 100 µs / min. 100 µs |