Switch Amplifier KFD2-SOT2-Ex1.LB

Switch Amplifier KFD2-SOT2-Ex1.LB
Switch Amplifier KFD2-SOT2-Ex1.LB

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 27751
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Passive transistor output, non-polarized
  • Passive fault output, non-polarized
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 acc. to IEC 61508
Параметр Значение
Общие характеристики
Артикул 27751
Control elements DIP-switch
Ripple ≤ 10 %
Switching frequency ≤ 5 kHz
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Rated voltage 20 ... 30 V DC
Electromagnetic compatibility NE 21:2004
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Marking II 3G Ex nA II T4
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Labeling space for labeling at the front
EU-type examination certificate DMT 01 ATEX E 133
IECEx approval IECEx PTB 05.0011
Approved for [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC
Rated current ≤ 50 mA
Output I signal, passive electronic output
Output II signal or error message; passive transistor output
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate TÜV 99 ATEX 1499 X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
Safety Integrity Level (SIL) SIL 2
Display elements LEDs
Configuration via DIP switches
Control drawing 116-0047
Galvanic isolation IEC 62103:2003
Signal level 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current ≤ 10 µA)
Connection side control side
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Signal type Digital Input
Rated values acc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Collective error message Power Rail