Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 85144 |
Ripple | ≤ 0.05 % of output signal range |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Rated voltage | 20 ... 35 V DC |
Power consumption | ≤ 2 W |
Deviation | ≤ 0.05 % of output signal range (current output), ≤ 10 µA at 20 °C (68 °F) |
Electromagnetic compatibility | NE 21:2006 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Current | 93 mA |
Marking | II 3G Ex nA II T4 Gc [device in zone 2] |
Output signal | 4 ... 20 mA , max. load 1000 Ω , for HART ≥ 230 Ω, Honeywell DE 230 ... 280 Ω (transmitter and communicator dependent) |
Dimensions | 20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1 |
Labeling | space for labeling at the front |
EU-type examination certificate | BAS 01 ATEX 7369 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Rise time | 10 µs |
Power | 587 mW |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Certificate | BASEEFA 09 ATEX 0218X |
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Display elements | LED |
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
Power dissipation | ≤ 1.6 W |
Control drawing | 116-0173 (cULus) |
IECEx certificate | IECEx BAS 06.0088 IECEx BAS 09.0102X |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex nA IIC T4 Gc |
Voltage | 25.2 V DC |
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Connection side | control side |
Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Signal type | Analog input |
Frequency range | field side into the control side: bandwidth with 1 mA signal 0 ... 40 kHz (-1 dB); 0 ... 50 kHz (-6 dB) safe area to hazardous area: bandwidth with 250 mV signal 2 Hz ... 40 kHz (-1 dB); 1 Hz ... 50 kHz (-6 dB) |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Output/power supply | functional insulation, rated insulation voltage 50 V AC |
Influence of ambient temperature | ≤ 20 ppm/K |
Input signal | 4 ... 20 mA |
Available voltage | approx. 17 V at 4 ... 20 mA |