Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

SMART Transmitter Power Supply KFD2-STC3-Ex1

SMART Transmitter Power Supply KFD2-STC3-Ex1
SMART Transmitter Power Supply KFD2-STC3-Ex1

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 85144
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • 2-wire SMART transmitter
  • Output 4 mA ... 20 mA
  • SMART capable up to 40 kHz (-1dB)
  • Suitable for Honeywell DE protocol
  • Terminals with test points
Параметр Значение
Общие характеристики
Артикул 85144
Ripple ≤ 0.05 % of output signal range
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Rated voltage 20 ... 35 V DC
Power consumption ≤ 2 W
Deviation ≤ 0.05 % of output signal range (current output), ≤ 10 µA at 20 °C (68 °F)
Electromagnetic compatibility NE 21:2006
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Current 93 mA
Marking II 3G Ex nA II T4 Gc [device in zone 2]
Output signal 4 ... 20 mA , max. load 1000 Ω , for HART ≥ 230 Ω, Honeywell DE 230 ... 280 Ω (transmitter and communicator dependent)
Dimensions 20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1
Labeling space for labeling at the front
EU-type examination certificate BAS 01 ATEX 7369
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rise time 10 µs
Power 587 mW
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate BASEEFA 09 ATEX 0218X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Display elements LED
Optional accessories - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)
Power dissipation ≤ 1.6 W
Control drawing 116-0173 (cULus)
IECEx certificate IECEx BAS 06.0088 IECEx BAS 09.0102X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex nA IIC T4 Gc
Voltage 25.2 V DC
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Connection side control side
Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Signal type Analog input
Frequency range field side into the control side: bandwidth with 1 mA signal 0 ... 40 kHz (-1 dB); 0 ... 50 kHz (-6 dB) safe area to hazardous area: bandwidth with 250 mV signal 2 Hz ... 40 kHz (-1 dB); 1 Hz ... 50 kHz (-6 dB)
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supply functional insulation, rated insulation voltage 50 V AC
Influence of ambient temperature ≤ 20 ppm/K
Input signal 4 ... 20 mA
Available voltage approx. 17 V at 4 ... 20 mA

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено