  • System board for Yokogawa CENTUM VP
  • For 32-channel DO card ADV551
  • For 32 modules
  • Recommended module: HiC2871 (DO)
  • 24 V DC supply
  • Hazardous area: spring terminals, blue
  • Safe area: Yokogawa system connector, 50-pin
Параметр Значение
Общие характеристики
Артикул 51874
Материал housing: polycarbonate
Ripple ≤ 10 %
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Storage temperature -40 ... 70 °C (-40 ... 158 °F)
Degree of protection IP20
Mass approx. 1200 g
Fusing 4 A , in each case for 32 modules
Electromagnetic compatibility NE 21:2012 For further information see system description.
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Voltage drop 0.9 V , voltage drop across the series diode on the termination board must be considered
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Output type volt-free contact
Dimensions 480 x 175 x 153 mm (18.9 x 6.9 x 6.02 inch) , height including module assembly
Reverse polarity protection yes
Core cross-section spring terminals: rigid: 0.2 ... 2.5 mm flexible: 0.25 ... 1.5 mm
EU-type examination certificate CESI 06 ATEX 022
IECEx approval IECEx CES 06.0003
Approved for [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I
Contact loading 30 V DC , 1 A
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000
Supply pluggable screw terminals , black
Display elements LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure
Field side explosion hazardous area: spring terminals , blue
Control side non-explosion hazardous area: Yokogawa system connector, 50-pin
Fault output pluggable screw terminals , black
Power dissipation ≤ 500 mW , without modules
Maximum safe voltage 250 V (Attention! U is no rated voltage.)
Nominal voltage 24 V DC , in consideration of rated voltage of used isolators
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V