Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

Resistance Repeater HiC2077

Resistance Repeater HiC2077
Resistance Repeater HiC2077

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 44773
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • 1-channel isolated barrier
  • 24 V DC supply
  • Resistance and RTD input (Pt100, Pt500, Pt1000)
  • Resistance output
  • Accuracy 0.1 %
  • Line fault detection (LFD) for Pt100
  • Up to SIL 2 acc. to IEC 61508
Параметр Значение
Общие характеристики
Артикул 44773
Control elements DIP-switch
Ripple within the supply tolerance
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Degree of protection IP20
Connection SL1: 8a(+), 10a(+), 7a(-), 9a(-)
Mass approx. 100 g
Rated voltage 20 ... 30 V DC bus powered via Termination Board
Power consumption 0.35 W (24 V and 1 mA sense current)
Deviation I ≥ 1 mA: ±0.1 % of R or ± 0.1 Ω (the larger value is applicable) I < 1 mA: accuracy reduces in proportion to I . e. g. I = 0.1 mA: ± 1 % of R or 1 Ω (the larger value is applicable).
Electromagnetic compatibility NE 21:2006 For further information see system description.
Mounting on Termination Board
Current 17.4 mA
Marking II 3G Ex nA II T4
Dimensions 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Labeling space for labeling at the front
EU-type examination certificate BASEEFA 10 ATEX 0263X
IECEx approval IECEx BAS 10.0122X IECEx BAS 10.0123X
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Rise time signal response time ≤ 2 ms (10 ... 90 %) response to application of I : R > 50 Ω and I < 5mA: < 5ms response to application of I : R > 30 Ω and I < 5mA: < 10ms response to application of I : R > 18 Ω and I < 5mA: < 20ms
Approved for [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I Ex nA II T4
Power 54 mW
Rated current < 20 mA
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Certificate BASEEFA 10 ATEX 0264X
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Display elements LED
Accuracy < ± 0.1 % of full-scale value
Fault signal < 18 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1mA)
Configuration via DIP switches
Control drawing 116-0333 (cULus)
Voltage 12.4 V
Maximum safe voltage 253 V (Attention! The rated voltage can be lower.)
Connection side control side
Input/Output safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Line fault detection 8 nA
Signal type Analog input
Input/power supply safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Output/power supply functional insulation, rated insulation voltage 50 V AC
Influence of ambient temperature I ≥ 1 mA, R ≥ 100 Ω : 0.01 %/K in the range -20 ... +60 °C (253 ... 333 K) I < 1 mA or R < 100 Ω: temperature stability reduces in proportion to I or R
Protection against electrical shock UL 61010-1
Coding pin 1, 3 and 4 trimmed For further information see system description.
Lead resistance ≤ 10 % of resistance value
Available voltage 0 ... 4.2 V
Transmission range 0 ... 10 mA