Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 72298 |
Mission Time (T | 20 a |
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm ... 2.5 mm for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm ... 1.5 mm |
Housing | PA 66-FR |
Mass | 160 g |
Electromagnetic compatibility | EN 61326-3-1:2008 |
Mounting | DIN mounting rail |
Interface type | RJ-45 socket, 8-pin Ethernet Programming interface |
Rated operating current | ≤ 200 mA from AS-Interface; ≤ 4 A from AUX |
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005/AC:2005 EN 61000-6-4:2007/A1:2011 |
Safety Integrity Level (SIL) | SIL 3 |
Supply | 24 V U |
Current loading capacity | 10 mA per signal output |
Rated operating voltage | 18,0 ... 31.6 V from AS-Interface |
UL File Number | E223772 |
Number/Type | Output circuits 1 and 2 max. contact rating: 700 m A at 24 V |
Performance level (PL) | PL e |
Functional safety | EN 61508:2010 and EN 62061:2005 (up to SIL3) EN 13849-1:2008/AC:2009 (PL e) |
PFH | 5.08 E-9 |
Input current | Static switching current: 4 mA at 24 V. Dynamic switching current: 15 mA at 24 V (T=100 μs) |
AS-Interface specification | V3.0 |
Insulation voltage | 500 V AS-Interface/U : |
AS-Interface | EN 62026-2:2013 |
Data decoupling | integrated |
Directive 2006/42/EC | EN 13849-1:2008/AC:2009 EN 62061:2005/A1:2013 |
Profile | configurable |
Auxiliary voltage (input) | 20 ... 30 V PELV |
LED O1, O2 | Status of outlputs, multicolored LED yellow: Output on |
LED AS-i M | Status of AS interface master, multicolored LED green: Master OK |
LED SM | Status of safety monitor, multicolored LED green: Safety monitor OK |
LED S1 ... S6 | Status of inputs S1 ... S6, yellow LED yellow: Contact open |
Application areas | Speed monitor: Local inputs, 1 to 2 axles up to 4 kHz |