Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

AS-Interface Gateway/Safety Monitor VBG-ENX-K30-DMD-S16

AS-Interface Gateway/Safety Monitor VBG-ENX-K30-DMD-S16
AS-Interface Gateway/Safety Monitor VBG-ENX-K30-DMD-S16

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 44340
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Gateway and safety monitor in one housing
  • Gateway compliant with AS-Interface specification 3.0
  • Connection to Ethernet Modbus TCP/IP
  • AS-Interface safety monitor with extended range of functions
  • Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
  • Memory card for configuration data
  • 2 AS-Interface networks
  • 2 safe output relays and 2 safe electronic outputs
  • Integrated switch allows line topology
  • DLR technology supports ring topology
Параметр Значение
Общие характеристики
Артикул 44340
MTTF 200 a
UL approval An isolated source with a secondary open circuit voltage of ≤ 30 V with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient temperature 0 ... 55 °C (32 ... 131 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP20
Mass 800 g
Electromagnetic compatibility EN 61000-6-2:2005, EN 61000-6-4:2007
Construction type Low profile housing , Stainless steel
Interface type Chip card slot
Transfer rate 19,2 kBit/s
Protocol EtherNet/IP + MODBUS TCP/IP acc. to IEEE 802.3 supports device level ring protocol DLR
B 2 E+7
Standards EN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e)
Response delay < 40 ms
Rated operating current ≤ 300 mA off AS interface network 1 ≤ 300 mA off AS interface network 2 ≤ 370 mA in total
Switch-on delay < 10 s
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Safety Integrity Level (SIL) SIL 3
Rated operating voltage 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V
UL File Number E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Number/Type 4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Performance level (PL) PL e
Safety output Output circuits 1 and 2: 2 potential-free contacts, 3  A at 30 V , 3 A at 30 V Output circuits 3 and 4: 2 PNP transistor outputs 0.5  A at 30  V
Button 4
AS-Interface specification V3.0
PLC-Functionality activateable
Duplicate address detection from AS-Interface slaves
Earth fault detection integrated
EMC monitoring integrated
Diagnostics function Extended function via display
Display Illuminated graphical LC display for addressing and error messages
LED ETHERNET ethernet active; LED green
LED AS-i ACTIVE AS-Interface operation normal; LED green
LED CONFIG ERR configuration error; LED red
LED PRG ENABLE autom. programming; LED green
LED POWER voltage ON; LED green
LED PRJ MODE projecting mode active; LED yellow
LED U AS-i AS-Interface voltage; LED green
LED AUX ext. auxiliary voltage U ; LED green
LED EDM/Start External device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuit Output circuit closed; 4 x green LEDs
Insulation voltage ≥ 500 V
Ethernet RJ-45
AS-Interface EN 62026-2:2013

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено