Параметр | Значение |
Общие характеристики | |
Артикул | 40576 |
MTTF | 200 a |
UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 V with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Degree of protection | IP20 |
Housing | Stainless steel |
Mass | 800 g |
Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-6-4:2007 |
Construction type | Low profile housing , Stainless steel |
Interface type | Chip card slot |
Transfer rate | 19.6 kbaud, no parity, 1 start bit, 1 stop bit, 8 data bits |
B | 2 E+7 |
Standards | EN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e) |
Response delay | < 40 ms |
Rated operating current | ≤ 200 mA from 24 V ≤ 45 mA from AS-Interface |
Switch-on delay | < 10 s |
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Shock resistance | EN 61131-2:2004 |
Safety Integrity Level (SIL) | SIL 3 |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface; 24 V |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
Number/Type | 4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs) |
Performance level (PL) | PL e |
Safety output | Output circuits 1 and 2: 2 potential-free contacts, max. contact load: 3 A at 30 V , 3 A at 30 V Output circuits 3 and 4: 2 PNP transistor outputs max. contact load: 0.5 A at 30 V |
Button | 4 |
AS-Interface specification | V3.0 |
PLC-Functionality | none |
Duplicate address detection | from AS-Interface slaves |
Earth fault detection | integrated |
EMC monitoring | integrated |
Diagnostics function | Extended function via display |
Display | Illuminated graphical LC display for addressing and error messages |
LED POWER | voltage ON; LED green |
LED AUX | ext. auxiliary voltage U ; LED green |
LED EDM/Start | External device monitoring circuit inputs closed, 4x yellow LEDs |
LED output circuit | Output circuit closed; 4 x green LEDs |
Insulation voltage | ≥ 500 V |
AS-Interface | EN 62026-2:2013 |
LED FAULT | Error display; red LED red: Communication error red flashing: release circuit error |
LED U AS-i 1 / U AS-i 2 | AS-Interface voltage - circuit 1/circuit 2; green LED |
LED ready | off: - constantly lit: startup/restart lock active flashing: external test required |