Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

AS-Interface sensor module VBA-4E-G11-ZAJ-V1

AS-Interface sensor module VBA-4E-G11-ZAJ-V1
AS-Interface sensor module VBA-4E-G11-ZAJ-V1

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 43817
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Inputs for 2-, 3-, and 4-wire sensors
  • Supply of sensors from AS-Interface
  • Function display for bus and inputs
  • Communication monitoring
  • Degree of protection IP68 / IP69K
  • AS-Interface POWER24
Параметр Значение
Общие характеристики
Артикул 43817
MTTF 120 a
Mission Time (T 20 a
Diagnostic Coverage (DC) 0 %
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP68 / IP69K
Connection AS-Interface: M12 round connector Inputs: M12 round connector
Housing PBT PC
Mass 200 g
Switching point according to DIN EN 61131-2 (Type 2)
Relative humidity 85 % , noncondensing
Altitude ≤ 2000 m above MSL
Mounting Mounting plate
Protection class III
Pollution degree 3
Vibration resistance 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Shock and impact resistance 30 , 11 ms in 6 spatial directions 3 shocks 10 , 16 ms in 6 spatial directions 1000 shocks
Rated operating current ≤ 40 mA (without sensors) / max. 240 mA
Emitted interference EN 61000-6-4:2007
Noise immunity EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Supply from AS-Interface
Fieldbus standard EN 62026-2:2013
Voltage 12 ... 31 V
Climatic conditions For indoor use only
Mounting screw Stainless steel 1.4305 / AISI 303
Tightening torque, housing screws 1.8 Nm
Current loading capacity ≤ 200 mA, overload and short-circuit protected
Rated operating voltage 18,0 ... 31.6 V from AS-Interface
UL File Number E223772
Number/Type 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Surge protection U : Over voltage category III, safe isolated power supplies (PELV)
Signal delay < 1 ms (input/AS-Interface)
Input current ≤ 9 mA (limited internally)
AS-Interface specification V3.0
AS-Interface EN 62026-2:2013
Slave type A/B slave
Required master specification ≥ V2.1
LED IN switching state (input); 4 LED yellow
0 (unattenuated) ≤ 3 mA
1 (attenuated) ≥ 5 mA
Input EN 61131-2:2007
Profile S-0.A.2
IO code 0
ID code A
ID1 code 7
ID2 code 2
D0 IN1 -
D1 IN2 -
D2 IN3 -
D3 IN4 -
P0 not used
P1 Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
P2 not used
P3 not used
Tightening torque, cable gland 0.4 Nm
LED AS-i/FAULT Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply overload

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено