Корзина 0 0
Электротехническое оборудование

Пт-Пн: 9:00 - 18:00

AS-Interface sensor/actuator module VBA-2E2A-G4-ZE/E2

AS-Interface sensor/actuator module VBA-2E2A-G4-ZE/E2
AS-Interface sensor/actuator module VBA-2E2A-G4-ZE/E2

Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ

артикул: 4117
Под заказ
Запрос цены

Доставка в любой регион России транспортной
компанией на Ваш выбор

  • Degree of protection IP67
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Flat or round cable connection (via standardized EEMS base, not included with delivery)
  • Cable piercing method for flat cable
  • Communication monitoring
  • Inputs for 2- and 3-wire sensors
  • Power supply of outputs from the external auxiliary voltage
  • Supply for inputs from AS-Interface
  • Function display for bus, inputs and outputs
  • LED indicator for overload on sensor supply
  • Detection of output overload
Параметр Значение
Общие характеристики
Артикул 4117
Ambient temperature -25 ... 60 °C (-13 ... 140 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Degree of protection IP67
Connection cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals
Housing PA 6 GF30
Mass 180 g
Switching point according to DIN EN 61131-2 (Type 2)
Relative humidity 85 % , noncondensing
Altitude ≤ 2000 m above MSL
Mounting DIN rail or screw mounting
Protection class III
Current 1 A per output
Pollution degree 3
Rated operating current ≤ 30 mA (without sensors) / max. 140 mA
Emitted interference EN 61000-6-4:2001
Noise immunity EN 61000-6-2:2001
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Supply from external auxiliary voltage U
Voltage ≥ (U - 0.5 V)
Climatic conditions For indoor use only
Tightening torque, housing screws 0.8 Nm
Current loading capacity ≤ 100 mA (T ≤ 40 °C), ≤ 75 mA (T ≤ 60 °C), overload-proof and short-circuit protected
Rated operating voltage 26.5 ... 31.6 V from AS-Interface
UL File Number E223772
Number/Type 2 electronic outputs, PNP overload and short-circuit proof
Surge protection U , U : Over voltage category III, safe isolated power supplies (PELV)
Input current ≤ 8 mA (limited internally)
AS-Interface specification V2.1
AS-Interface EN 62026-2:2013
Slave type A/B slave
Required master specification ≥ V2.1
LED PWR/FAULT dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs
LED IN switching state (input); 2 LED yellow
0 (unattenuated) ≤ 2 mA
1 (attenuated) ≥ 4 mA
Input EN 61131-2:2007
Profile S-B.A.0
IO code B
ID code A
ID1 code 7
ID2 code 0
D0 - OUT1
D1 - OUT2
D2 IN3 -
D3 IN4 -
P0 not used
P1 not used
P2 not used
P3 not used
Auxiliary voltage (output) 24 V DC ± 15 % PELV
LED OUT Switching state (output); 2 LED yellow

Техподдержка

Опишитите свой вопрос, специалист службы технической поддержки свяжется с Вами в течении нескольких часов

Отправляя заявку, вы принимаете условия Политики конфиденциальности.

Спасибо!

Ваше сообщение успешно отправлено