Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 42130 |
Control elements | Control panel |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | 300 g |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
Power consumption | 2.5 W / 4 VA |
Input frequency | rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz |
Electromagnetic compatibility | NE 21:2006 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Measurement range | 0.001 ... 1000 Hz |
Resolution | < 10 µA |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Mechanical life | 5 x 10 switching cycles |
Labeling | space for labeling at the front |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Response delay | ≤ 200 ms |
Rated current | approx. 130 mA |
Contact loading | 40 V DC |
Directive 2014/30/EU | EN 61326-1:2006 |
Display elements | LEDs , display |
Accuracy | < 30 µA |
Power dissipation | 2.2 W / 3.5 VA |
Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Configuration | via operating buttons via PACTware |
Directive 2014/35/EU | EN 61010-1:2010 |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) |
Connection side | control side |
Input | EN 60947-5-6:2000 |
Load | max. 650 Ω |
Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 4 mA |
Open loop voltage | max. 24 V DC |
Signal type | Digital Input |
Open circuit voltage/short-circuit current | 18 V / 5 mA |
Switching point/switching hysteresis | logic 1: > 2.5 mA ; logic 0: < 1.9 mA |
Pulse duration | min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs |
Measuring time | frequency measurement: < 100 ms |
Programming interface | programming socket |
Influence of ambient temperature | 0.005 %/K (50 ppm) |
Input I, II | 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA |
Output I, II | signal, relay |
Output III and IV | signal , electronic output, passive |
Output V | analog |
Current range | 0 ... 20 mA or 4 ... 20 mA |
Interface | RS 232 |
Input I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Input III, IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Mutual output I, II, IV | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Output III, IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Output III, IV/input III, IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
Output III, IV/V | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |
Output V/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V |
Interface/output III, IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 V |