Для оформления заявки добавьте оборудование
в корзину и сформируйте заказ
Доставка в любой регион России транспортной
компанией на Ваш выбор
Параметр | Значение |
Общие характеристики | |
Артикул | 96978 |
Operating voltage | 20 ... 30 V DC , ripple 10 % ; 12 ... 20 V DC sensitivity reduced to 80 % |
No-load supply current | ≤ 20 mA |
Switching frequency | 100 Hz |
UL approval | cULus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated ≤36 V |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Degree of protection | IP67 |
Housing | Polycarbonate |
Mass | Per 10 g |
Time delay before availability | ≤ 150 ms |
Voltage drop | ≤ 2 V |
Pulse length | ≥ 3 s |
Output type | 1 switch output E0, NPN, NO |
Vibration resistance | 10 ... 55 Hz , Amplitude ± 1 mm |
Connection type | M8 x 1 connector , 4-pin |
Off-state current | ≤ 0.01 mA |
Standards | EN 60947-5-2:2007+A1:2012 IEC 60947-5-2:2007 + A1:2012 |
LED green | Power on ( emitter ) |
LED yellow | switching state ( receiver ) |
Sensing range | 0 ... 800 mm emitter/receiver spacing |
Tightening torque, fastening screws | max. 0.2 Nm |
Standard target plate | see table |
Transducer frequency | approx. 300 kHz |
Input type | 1 program input (receiver) |
Transducer | epoxy resin/hollow glass sphere mixture; polyurethane foam |
Rated operating current | 200 mA , short-circuit/overload protected |
Switch-on delay | ≤ 5 ms |
Shock resistance | 30 g , 11 ms period |
Rated operating voltage | 24 V DC |
Permissible cable length | max. 300 m |
Level | low level : 0 ... 0.7 V ; high level : > 14 V |
Input impedance | 16 kΩ |
Installation position | any position |